Low subcool high superheat - 8-12* superheat would be what you want to shoot for. higher the superheat, the more starved the evaporator is. you definitely have to factor in them long linesets. if you can get the superheat down to the margin, roll with it. you will know your overcharged if your superheat falls below the margin.

 
 By keeping an eye on both subcooling and superheating, you can optimize your refrigeration system’s efficiency, prolong its life, and minimize energy consumption. Navigating through this hub page, you have learned the importance of maintaining the ideal superheat range, as both high and low superheat can cause potential problems in your system. . Hair salon germantown ave philadelphia

If you look at the bottom of the post, where I detail what high or low superheat and subcool can mean, it'll help lead you in the correct direction for diagnostics. For example, a no-cool on a residential split with a txv, where your data plate calls for 10f subcooling, and your system is at 10f subcooling but has a 28f superheat, you know the ...Bumping is an occurrence in chemistry where liquids boiled in a test tube superheat before undergoing a sudden release of vapor, expelling the liquid from the container. Bumping is...Superheat Good Subcool Good High SH Low SC ... High Low Low Low High Over-Charge High High Restricted Low Low Over-feeding Only evaluate charge after the airflow has been confirmed to be accurate and coils are confirmed to be clean. College of HVAC Education . Title: Microsoft Word - Thumb Chart complete.doc ...High superheat refers to a value of superheat that's higher than recommended. As an example: If a system with a target superheat of 10deg is running a 28deg superheat, it has a high superheat. Superheat is the difference between the suction line temperature and the suction saturation temperature, so it's a subtraction of those two numbers. IE:High discharge pressure, high suction pressure. with high super heat and subcooling; Cookie Consent We use cookies to improve your website experience. ... I have 325psi on the high side and 87psi on the low side. The superheat is 31 degrees and the sub cooling is 40 degrees. It does not have a txv. Reply . 07-27-2011, 09:01 PM #6. hvacjamie.Refrigerant undercharge: When there is not enough refrigerant in the system, it can result in low suction pressure, low head pressure, high superheat, and high sub-cool. Restriction in the refrigerant line: A physical blockage in the refrigerant line can cause reduced suction and head pressure, as well as imbalances in the system.If I have my theroy right I have a low superheat of 10 and a high subcooling of 21. Ambiant temp outside is 81 and all temps are in F. 19-07-2011, 03:16 AM #40. Gary. View Profile View Forum Posts View Blog Entries Visit Homepage View Articles VIP Poster Join Date Apr 2001 Location New Port Richey, Florida - USA ...When the device overfeeds, there are high chances for both the suction pressure and the discharge pressure to increase. 3. Reduced airflow through the evaporator. One of the most common reasons for low superheat is due to reduced airflow. With reduced airflow, there isn’t enough warm air to vaporize the refrigerant.Steam at 213 degrees F is superheated by 1 degree F. Superheat is then any temperature of a gas above the boiling point for that liquid. When a refrigerant liquid boils at a low temperature of 40 degrees in a cooling coil and then the refrigerant gas increases in temperature, superheat has been added. If this refrigerant changed from a liquid ...High superheat low subcooling is when there is a limited flow of refrigerant in the evaporator and a limited flow of the refrigerant in the condenser. It is worth noting that in systems with liquid line receivers, subcooling will not increase because the liquid will go to the receiver instead of the condenser although the receive line filter is ...What causes Low superheat with high subcool. When both low superheat and high subcooling occur simultaneously, it signals a unique condition that can only be attributed to an overall excess of refrigerant in the system. Overcharging the air conditioning system with refrigerant is the primary cause of experiencing both low superheat and high ...System Information R22 2.5 ton: Low Side: 115. High Side: 240. Return Air: 83. Suction Line Temp: 75. Measured Super heat: 5. Super heat should be around 15. Low superheat is an indication that liquid refrigerant not changing state in the evaporator and is possibly flooding back to the compressor.Post Likes. Low subcooling results when there is insufficient refrigerant to fill the lower part of the condenser coil. High suction superheat results when there is insufficient refrigerant to fill the evaporator properly. If you have insufficient refrigerant in both places - it is likely that the system is undercharged.At a high level, superheat occurs when you heat vapor above its boiling point. Subcooling occurs when you cool a vapor below the temperature at which it turns into a liquid. But let's dive in deeper, starting with superheat. Boiling is when a liquid gains heat and transforms into a vapor. Remember, superheat occurs when you heat vapor above ...1. Connect the manifold gauge set to the low and high side service valves. 2. Introduce nitrogen into the system until the pressure increases to 125 psig and check for leaks. Repair any leaks and recheck before proceeding. 3. Remove (Bleed) the nitrogen from the system: connect the micron gauge and vacuum pump. High superheat= not enough refrigerant in the evaporator. Low subcool= not enough refrigerant in the condenser Compression ratio is fine, unlikely to be the valves. It isn’t possible for you to have liquid refrigerant in the liquid line if the line is hotter than the boiling point of the refrigerant. A Negative subcool number is not a thing. Sometimes adjusting the superheat will make it feed more and you will need to add a bit more refrigerant. On the other hand, if the unit has a fixed orifice, then subcooling can be very important, and you have little room to play with superheat. You see, each system will have it's own criteria for charging.Actual measured superheat is by 2°F or more degrees higher than the target superheat; this is considered high superheat. Actual measured subcooling is by 3°F or more …Subcooling is a measurement of temperature DECREASE of a liquid below its saturation (mixed liquid/vapor) temperature at a given pressure. For example, water boils at 212° Fahrenheit at sea level (atmospheric pressure of 14.7 PSIA). If water is 212°F and at atmospheric pressure at sea level, you can be sure it is at saturation, which means it ...High suction pressure,superheat, and low subcooling. Low suction pressure, low super heat and low subcooling. ... High suction pressure, high superheat, and low subcoomng. 41 of 44. Term. How can moisture in the refrigeration system affect the metering device? contact of the expansion valve bulb. operation of the metering device.Jul 24, 2018 · From the Goodman manual for that model. Outside drybulb 95F inside drybulb 80F. Hi pressure = 335 Psig, Lo pressure 130 Psig. Which is 20-30 psi off on both. But I was under the assumption if it where low on 410a there would be high superheat and high subcooling. Like I said I’m new. With the excessive subcooling and no superheat, I am confused. If I have my theroy right I have a low superheat of 10 and a high subcooling of 21. Ambiant temp outside is 81 and all temps are in F. 19-07-2011, 03:16 AM #40.Take the condensing temperature and the condenser outlet temperature, and the difference between the two is the amount of subcooling. "Let's say the condensing temperature is 100°F. Put a thermistor on the condenser outlet, and let's say that's 90°," continued Tomczyk. "So, you have 10° of subcooling. Technicians get confused ..."Superheat and subcooling simply tell us where the refrigerant is located. Too much refrigerant on the high side and too little on the low side indicates a restriction. ... I don't mean "high super heat low subcooling low charge" or low super heat high subcooling overcharge" I need to have an understanding so I can determine why the ...Refrigerant undercharge: When there is not enough refrigerant in the system, it can result in low suction pressure, low head pressure, high superheat, and high sub-cool. Restriction in the refrigerant line: A physical blockage in the refrigerant line can cause reduced suction and head pressure, as well as imbalances in the system.The system will have symptoms of low suction pressures, high evaporator and compressor superheats, normal-to-high condenser subcooling, low compressor amp draws, and low head pressures. ... Evaporator superheat: 40°F: Compressor superheat: ... All of the liquid in the condenser will probably sit there for a while and subcool because …The outside aor could make the sc high if it is cool out side but low if the outside air is higher. The system needs to run for 20-30 min, to let the system even out. If there is a heavy load on the system too that could cause a low subcooling and a high superheat .. Just some thoughtThe difference of the two temperatures is the subcooling value. Trouble diagnosis Data from superheat and subcooling measurements can be useful for determining various conditions within the HVAC/R system, including the amount of refrigerant charge and verifying the operating condition of the metering device. These measurements can also be used ...Superheat and subcooling data can help you pinpoint these issues quickly. Common Causes of Superheat and Subcooling Imbalance. Common reasons for superheating and subcooling include issues such as liquid line restriction, malfunctioning metering systems, and limited airflow, all of which can lead to high superheating and low subcooling levels. 1.1. Low Refrigerant Charge (Low Subcooling) Or High Refrigerant Charge (High Subcooling) 2. Oversized Metering Device (Low Subcooling) Or Undersized Metering …If superheat is low and sub-cooling is high: Charge must be adjusted. System overcharged If superheat is high and sub-cooling is high: Could have blockage in coil, orifice or line set. If superheat is low and sub-cooling is low: Orifice could be too big, there is no orifice in the unit of the orifice is stuck and refrigerant is by-passing it.High suction pressure. One sign of low subcooling is high suction pressure in your HVAC system. When there’s not enough subcooling, the refrigerant pressure in the system can become elevated, which can lead to poor cooling performance and potential damage to your system. Low discharge pressure. Low discharge pressure is another sign of low ...High superheat low subcooling on a TXV system means that there is no sufficient amount of refrigerant in the evaporator and there is low amount of the refrigerant in the condenser unit. This condition is mainly caused by low charge in an air conditioning system and can be fixed by sealing leaks and adequately charging the system with a …I come back the next day expecting to have to pull charge out and the subcool being way high. The unit cooled the house down to 70 it's probably 85 outside. These are my readings 296psi high side, 95.8 lstat, 93.6 line temp, 2.3 subcool. 140.6psi low side, 50.1 vstat, 51.3 line temp, 1.2 superheat. 20degree delta tee across the return and supply.If I have my theroy right I have a low superheat of 10 and a high subcooling of 21. Ambiant temp outside is 81 and all temps are in F. 19-07-2011, 03:16 AM #40. Gary. View Profile View Forum Posts View Blog Entries Visit Homepage View Articles VIP Poster Join Date Apr 2001 Location New Port Richey, Florida - USA ...Which would suggest 26 is high for the superheat and 61 is way high for the subcooling. The suction pressure and SST is normal, but 350 could be high for the head depending on the unit SEER. Residential 13 SEER equipment would be closer to 300 for an 80 degree ambient. It's about right for 10 SEER.Low capacity, a starved evaporator, high superheat, and low suction pressure are all symptoms of a(n) _____. ... high subcooling and high compression ratios are all symptoms of a(n) _____. refrigerant overcharge. All reciprocating compressors should immediately go into a vacuum if the suction line is valved off when the compressor is running ...Low subcooling means you won’t have enough liquid refrigerant to feed your expansion valve. High subcooling means you may have to much refrigerant in the system or you have a subcooling circuit in the system that helps subcool the liquid refrigerant more. I’ve seen subcooling circuits on chillers and VRF/VRV systems.If superheat is low and sub-cooling is high: Charge must be adjusted. System overcharged If superheat is high and sub-cooling is high: Could have blockage in coil, orifice or line set. If superheat is low and sub-cooling is low: Orifice could be too big, there is no orifice in the unit of the orifice is stuck and refrigerant is by-passing it.Stress hormones released due to low blood sugar can lead to anxiety. Monitoring your food intake and support from a mental health professional may help. Stress hormones released du...3. Airflow through the evaporator is too high. When there is an excess flow of air through the evaporator coil, the capability of the system to remove moisture is reduced. The vapor picks up more than usual heat which causes the suction pressure to be higher than normal pressure and has a higher superheat. 4.Steam at 213 degrees F is superheated by 1 degree F. Superheat is then any temperature of a gas above the boiling point for that liquid. When a refrigerant liquid boils at a low temperature of 40 degrees in a cooling coil and then the refrigerant gas increases in temperature, superheat has been added. If this refrigerant changed from a liquid ...A superheat that is too low risks going to zero and causing compressor damage by flooding the compressor. A superheat that is too high means that the evaporator coil is being underfed with refrigerant, which will lead to low capacity, low efficiency, and compressor overheating on most systems. ... superheat, and subcooling in far greater detail.Low subcooling and high superheat are both conditions that can occur in a refrigeration system and indicate a problem with the system's balance. Low subcooling means that there is an insufficient amount of refrigerant in the condenser, which is the part of the system where the refrigerant releases the heat it has absorbed from the evaporator. ...When the device overfeeds, there are high chances for both the suction pressure and the discharge pressure to increase. 3. Reduced airflow through the evaporator. One of the most common reasons for low superheat is due to reduced airflow. With reduced airflow, there isn’t enough warm air to vaporize the refrigerant.Jul 8, 2022 · High superheat low subcooling is when there is a limited flow of refrigerant in the evaporator and a limited flow of the refrigerant in the condenser. It is worth noting that in systems with liquid line receivers, subcooling will not increase because the liquid will go to the receiver instead of the condenser although the receive line filter is ... Superheat and subcooling are fairly easy to understand once you get the science behind it. Both are relative to saturation temperature. Saturation temperature is the temperature at which a substance transitions between liquid to vapor. So imagine water which usually has a saturation temperature of 212*. The liquid water below 212* is subcooled.Lowes.com is the official website of Lowe’s Companies, Inc., one of the largest home improvement retailers in the world. The website was launched in 1996 as a way for customers to ... Superheat and Subcooling are technical readings in an HVAC that measure the Freon (refrigerant) reading. Superheat measures the Freon boiling point in gas form while subcooling measures the Freon in liquid form below the evaporation level. To calculate superheat and subcooling measurements, a specific Mathematical chart is used, and the process ... Maryland. Posts. 9. Post Likes. Low Subcooling Low Superheat? I am working on a two stage heat pump with a varable speed air handler. The system runs about 1.5 deg S/C and about 2 deg S/H The delta T is 22 deg. A capacity check shows systems is operation at 122% of publish Capacity. Adding refregerant does not change the S/C much at all.Actual measured superheat is by 2°F or more degrees higher than the target superheat; this is considered high superheat. Actual measured subcooling is by 3°F or more …What is superheat and Subcool? While superheat indicates how much refrigerant is in the evaporator (high superheat indicates not enough, low superheat indicates too much), subcooling gives an indication of how much refrigerant is in the condenser. Subcooling on systems that use a thermostatic expansion valve (TXV) should be approximately 10F to ...If the superheat is too high and the subcooling is too low, you'll need to add more refrigerant to the system. 4. To do this, attach a charging hose to the system's low-pressure side and open the valve. 5. Slowly add refrigerant to the system until the superheat and subcooling are within the desired range. 6.In this video, see how to use the superheat and subcooling troubleshooting procedure to evaluate a refrigeration or air conditioning system. To learn about t...Apr 18, 2017 ... In this HVAC Refrigerant Charging Video I go over what it means to have low R-22 Freon or Low R-410A Suction Vapor Pressure along with a Low ...New Guys: know your superheat & subcooling like the back of your hand & know how to calculate it without digital gauges. DON'T BE THAT GUY!!!IF YOU HAVE ANY ...Signs of Low Subcooling High suction pressure. One sign of low subcooling is high suction pressure in your HVAC system. When there’s not enough subcooling, the refrigerant pressure in the system can become elevated, which can lead to poor cooling performance and potential damage to your system. Low discharge pressureWelcome to Enertech University, online training by Enertech. Measuring subcooling and superheat is a critical diagnostic testing procedure when a unit is not...In today’s digital age, convenience is key. Whether it’s shopping for groceries or paying bills, more and more people are turning to online platforms to simplify their daily tasks....First, measure the superheat right at the evaporator outlet in the same general location as the TXV bulb and equalizer. In most cases, the superheat at that point should be 5-10 degrees, but refer to the manufacturer's specs when in doubt. In some cases, you will not have a pressure port at the evaporator, so you must rely on a …Normal to high subcooling + high superheat = possible restriction or bad txv - only if your temp readings are accurate. I doubt they are. Use real thermometers, no temperature gun. ... LOW CHARGE = High superheat. Low suction pressure, indoor TD, subcooling, head pressure & compressor current draw. OVER CHARGE = Low superheat. Normal indoor TD.the low side. o Low superheat with high subcooling indicates an overcharge. Too much liquid on both sides. o High superheat with low condenser subcooling indicates an undercharge. Not enough liquid on either side. Low side superheat and condenser subcooling simply tell us where the refrigerant is located.1. Low Refrigerant Charge (Low Subcooling) Or High Refrigerant Charge (High Subcooling) 2. Oversized Metering Device (Low Subcooling) Or Undersized Metering …However, if the superheat is too high, it's a sign that the refrigerant has boiled off too soon. This scenario is often caused by the system being low on charge or (very rarely) by too much airflow across the indoor coil. Subcool is measured at the outlet of the condenser coil and it is the sensible temperature decrease after saturation.high subcooling means liquid refrigerant is in the condenser getting cooled off, low flow of this liquid means it keeps getting cooled and the subcooling goes higher. high superheat, when the evap is empty super heat goes up. when these two happen we have a restriction on the liquid line (valve partially closed ), filter drier, or a bad weld ...What would cause an AC unit to have low superheat and low Subcooling? It was an 80F day and my low pressure was 90 and my head pressure was 263. Now I did added refrigerant but that just made my low pressure go lower and my superheat to go lower. My suction temp was 32 and my evap was 30. System is a 2 ton with a txv and air flow is adjusted for a 2 ton my static pressure is 0.49 across the ...Superheat = Current Temperature - Boiling Point. Superheat is measured by its temperature above its boiling point. If a refrigerant vapor boiling point is 140 degrees, for example, then anything about that pressure would be too high for that specific refrigerant. To calculate the measurement of subcooling, the formula is: Subcooling = Boiling ...High superheat low subcooling is when there is a limited flow of refrigerant in the evaporator and a limited flow of the refrigerant in the condenser. It is worth noting that in systems with liquid line receivers, subcooling will not increase because the liquid will go to the receiver instead of the condenser although the receive line filter is ...The model ASX14 superheat and subcooling accessory head measures refrigerant pressure and temperature simultaneously. It then calculates and displays superheat or subcooling. It has a 1/4" industry standard fitting for actual pressure. A pipe clamp thermocouple is included for temperature. Select R22 or R410A. Select superheat or subcool-It is imperative that we use low-loss fitting on our hoses. Pressure Readings: Observe the low pressure and high pressure readings on the manifold gauge; these will be the predominant black numbers around the perimeter for analog gauges. Take note of the corresponding saturation temperatures for each.Superheat determines by how many degrees of temperature refrigerant vapor increases in the system. We are usually looking for 7°F to 15°F superheat.Too low superheat (below 2°F) = Risk of flooding the compressor, too high superheat (above 15°F) = Risk of overheating the compressor.More about that in our general superheat and subcooling article here.Airflow. Low suction pressure, txv is trying to maintain superheat, subcooling means liquid should be hitting the valve. I would get it 10-12 SC just to make sure but I doubt it would help in this case. 20 degree split also says it's not refrigerant related. Check static pressure and blower wheel. If static is high, it's duct work.The nucleate boiling suppression factor, S, is the ratio of the effective superheat to wall superheat. It accounts for decreased boiling heat transfer because the effective superheat across the boundary layer is less than the superheat based on wall temperature. The two-phase multiplier, F, is a function of the Martinelli parameter χ tt.High subcooling is usually accompanied by high head pressure because liquid is displacing available condensing area. Low superheat, low evaporator load - dirty filter, slipping belt, low fan speed, filthy coil. High superheat, evaporators being starved for refrigerant if suction pressure is low. If suction pressure is high and superheat seems ...Sep 6, 2018 · I come back the next day expecting to have to pull charge out and the subcool being way high. The unit cooled the house down to 70 it’s probably 85 outside. These are my readings 296psi high side, 95.8 lstat, 93.6 line temp, 2.3 subcool. 140.6psi low side, 50.1 vstat, 51.3 line temp, 1.2 superheat. 20degree delta tee across the return and supply. High Suction - Low Superheat and No Subcooling 2.5 ton lennox condenser 3 ton drive on blower 3.5 ton evap 50 evap 45 SLT 100 condensing temp 105 LLT ... Elevated suction, low superheat, lowish head and low subcooling are typically symptoms of an overfeeding metering device. But 10 SC and 7 SH are reasonable numbers though 7 SH is probably ...Terms in this set (8) find the low side pressure and convert it to the saturation temp. measure the suction line temp with thermometer. Superheat = suction line temp - saturation temp. find the high side pressure and convert it to the saturation (condensing point) temp. measure the liquid line temp. Subcooling = saturation temp - liquid line temp.That means understanding and measuring all three types of superheat: evaporator, total, and duct system. 1. Evaporator superheat. To measure evaporator (indoor coil) superheat, first measure the suction line temperature at the evaporator outlet. Next, measure the refrigerant pressure at the suction line of the indoor coil.Take the condensing temperature and the condenser outlet temperature, and the difference between the two is the amount of subcooling. “Let’s say the condensing temperature is 100°F. Put a thermistor on the condenser outlet, and let’s say that’s 90°,” continued Tomczyk. “So, you have 10° of subcooling. Technicians get confused ...Superheat and subcooling questions. Well I went to College for HVAC and was thought a general rule that subcooling usually is between 10-20 degrees, and superheat is 8-12 degrees. I know some units recommend subcooling on the name plate for that unit. Saw some guys running like 6 degrees subcooling and 17 degrees superheat...What does a normal superheat (10 degree) with a low subcool temp (zero degrees) mean? It is a nice day out and outdoors is only at 82. Cant imagine service tech checked the system and left it undercharged. ... the refrigerant charge would actually be very low, but without the usual low suction pressure/high superheat symptoms. Superheat and Subcooling are technical readings in an HVAC that measure the Freon (refrigerant) reading. Superheat measures the Freon boiling point in gas form while subcooling measures the Freon in liquid form below the evaporation level. To calculate superheat and subcooling measurements, a specific Mathematical chart is used, and the process ... Superheat and Sub-Cooling. Whenever an HVAC technician needs to add refrigerant to a system or adjust the charge the tech needs to know what superheat and/or sub-cooling is to properly ensure the refrigerant charge is correct. It is also important to have a pressure-temperature or PT Chart to properly read the pressures and temperatures.

Low capacity, a starved evaporator, high superheat, and low suction pressure are all symptoms of a(n) _____. ... high subcooling and high compression ratios are all symptoms of a(n) _____. refrigerant overcharge. All reciprocating compressors should immediately go into a vacuum if the suction line is valved off when the compressor is running .... Corningware plates vintage

low subcool high superheat

Anything above the boiling point is all vapor, and it's superheated. Very high superheat indicates that the refrigerant boiled off very early in the evaporator, meaning that the system could be low on charge. On fixed-orifice systems, you charge a system via superheat. Zero superheat indicates that you have liquid in the suction line.If the superheat is too high, the system will be inefficient. ... If the superheat is too low, you risk flooding the compressor. ... Subcooling is another method to improve the efficiency of the refrigeration cycle. We can define subcooling as the difference between the condensation temperature and the temperature at the inlet of the expansion ...Liquid line temp 101 degrees and the suction was 49 degrees. The low subcooling and low suction pressure indicate low airflow. The somewhat low deltaT seems to contradict that. Could be a significant amount of air bypassing the coil based on your report, which would account for all of the numbers that you posted.Superheat / Subcooling #1. Teacher 16 terms. James_Morrill. Preview. IST midtern. 25 terms. Madelyn__Medeiros. ... measure the high side pressure at the condenser outlet and convert that pressure to temperature by using the PT Chart. Measure the actual temperature at the condenser outlet location and compare the two. ... The low Pressure gauge ...Low suction pressure and high head pressure is a condition where there is a decreased refrigerant pressure in the AC system and at the same time a high output pressure in a compressor. This condition is mainly caused by a defective or malfunctioning TXV valve. An expansion valve is a device that regulates the flow of the liquid refrigerant …High superheat refers to a value of superheat that's higher than recommended. As an example: If a system with a target superheat of 10deg is running a 28deg superheat, it has a high superheat. Superheat is the difference between the suction line temperature and the suction saturation temperature, so it's a subtraction of those two numbers. IE:From the Goodman manual for that model. Outside drybulb 95F inside drybulb 80F. Hi pressure = 335 Psig, Lo pressure 130 Psig. Which is 20-30 psi off on both. But I was under the assumption if it where low on 410a there would be high superheat and high subcooling. Like I said I’m new. With the excessive subcooling and no superheat, I … High superheat refers to a value of superheat that's higher than recommended. As an example: If a system with a target superheat of 10deg is running a 28deg superheat, it has a high superheat. Superheat is the difference between the suction line temperature and the suction saturation temperature, so it's a subtraction of those two numbers. IE: And yes, you can have too much subcool, but don't want to since it will, as been talked about before "destroy" the capacity of your system! and will lower the capacity of your condensor. Last edited by Lowrider; 03-03-2007 at 10:05 PM . 04-03-2007, 06:23 AM #15. Gary.The following can, in theory, cause high subcooling, but effects are minimal: Low condenser air flow on TXV metering; High ambient on TXV metering; Low subcooling (aka a "starved condenser") can be caused by many things, but some culprits to check are: Low charge; Long liquid lines; High vertical separation; Liquid lines exposed to high ...If the actual subcooling is higher than the target subcooling, the unit’s refrigerant charge level is overcharged. Some refrigerant will need to be recovered into a recovery bottle. • Actual Subcooling +/-3° F Target Subcooling = Correct Refrigerant Level. • Actual Subcooling < Target Subcooling = Add Refrigerant.Superheat that is too low or too high may cause damage to a compressor. A refrigerant with a 0°F superheat value (saturated refrigerant) at this location indicates that some amount of liquid refrigerant is returning to the compressor. In this condition, the amount of liquid refrigerant returning is unknown, but any amount is too much. ...If I have my theroy right I have a low superheat of 10 and a high subcooling of 21. Ambiant temp outside is 81 and all temps are in F. 19-07-2011, 03:16 AM #40. Gary. View Profile View Forum Posts View Blog Entries Visit Homepage View Articles VIP Poster Join Date Apr 2001 Location New Port Richey, Florida - USA ...The main reasons your compressor will have simultaneously low head pressure and high suction pressure is due to: Bad or leaky compressor valves. Worn compressor piston rings. Leaky oil separator return line. Your compressor valves may become inefficient due to poor sealing from dirt and debris deposits.Q-Chat. jaketomas111. Study with Quizlet and memorize flashcards containing terms like What is superheat?, What is subcool?, How do we find superheat? and more.Low Subcool. High Superheat (potentially) Low Evaporator Delta T. Poor Dehumidification due to high coil temperature. Low compressor amps. Low Compression Ratio. Low Discharge Temperature. Low Approach (liquid line temperature above outdoor temperature) High Efficiency (EER/SEER) High Stage (5-ton)Jul 26, 2021 · 20°F. Notice the 30°F of liquid subcooling backed up in the condenser in this overcharged system. Because of this overcharge, the condenser will have too much liquid backed up in its bottom, causing high condenser subcooling. With an overcharge, increased liquid subcooling amounts will be realized in the condenser. Total Superheat with R22 = Corresponding temperature at suction pressure - Temperature measured at a suction line or outlet of the evaporator. The superheat is nearby 10 ° F in most cases. If the superheat is high, then it causes an increase in the heat of compression. This increase in temperature can affect the performance of the compressor..